Parameter Description
VD300 Series Inverter User Manual
- 150 -
The above parameters are used to set the run time of each stage and the Acceleration/deceleration
time of each stage in simple PLC operation, the run frequency of each stage and run direction is
corresponding to each stage of MS speed. If one stage run time is 0, then no matter how operating
frequency is this stage will be jumped over, if one stage run time is not 0 but run frequency is 0, the
inverter will keep output as zero frequency within this stage.
P11.52
Acceleration /
Deceleration Time
Selection Mode of
Multi-stage Speed
0: Function code to determine
1: Terminal to determine
0
○
Selecting MS speed of Acceleration deceleration time can decided by simple PLC corresponding to
each section of acceleration and deceleration time, can also be decided by the 4 acceleration and
deceleration time selected by terminal DI (can refer to group P5 in Schedule 2 --acceleration and
deceleration time select terminal function explanation).