VD300 Series Inverter User Manual
Parameter Description
- 121 -
P06.20
AO2 Output Filter Time
0.000s~10.000s
0.000s
○
The function code used to set the relation of analog output voltage and its representing set value.
When AO1, AO2 output is the current output, 1mA current is equal to 0.5V voltage, so 20mA current
equal to10V.
When AO1 AO2 output is current output, it is suggested to add external resistor with less than 500Ω.
P06.21
HDO1 Output Voltage
(Current) Lower Limit
0.0%~P06.23
0.0%
○
P06.22
Lower Limit
Corresponding HDO1
Output
0.00kHz~100.00kHz
0.0kHz
○
P06.23
HDO1 Output Upper
Limit
P06.21~100.0%
100.0%
○
P06.24
Upper Limit
Corresponding HDO1
Output
0.00kHz~100.00kHz
50.00kHz
○
P06.25
HDO1 Output Filter Time
0.000s~10.000s
0.000s
○
When selecting HDO1 terminals as pulse output, the function code is used to set value between the
high-speed pulse output and its representative set value.
P06.26
DO1 Terminals Closed
Delay
0.0s~6000.0s
0.0s
○
P06.27
DO1 Terminals Open
Delay
0.0s~6000.0s
0.0s
○
P06.28
HDO1 Terminals Close
Delay
0.0s~6000.0s
0.0s
○
P06.29
HDO2 Terminals Open
Delay
0.0s~6000.0s
0.0s
○
P06.30
Relay T1 Close Delay
0.0s~6000.0s
0.0s
○
P06.31
Relay T1 Open Delay
0.0s~6000.0s
0.0s
○
P06.32
Relay T2 Close Delay
0.0s~6000.0s
0.0s
○
P06.33
Relay T2 Open Delay
0.0s~6000.0s
0.0s
○
P06.34
DO5 Terminals Close
Delay
0.0s~6000.0s
0.0s
○
P06.35
DO5 Terminals Open
Delay
0.0s~6000.0s
0.0s
○
Set output terminal DO1, HDO1, Relay T1, Relay T2 delay time from status change to actual output
change. As below diagram:
Содержание VD300 Series
Страница 2: ......