VD300 Series Inverter User Manual
Function Parameter Table
- 67 -
power off
0: Save when power off
1: Clear when power off
P09.46
PWM Selection
0x00~0x21
LED unit’s digit: PWM mode selection
0: PWM mode 1, PWM mode1, 3phase
modulation and 2phase modulation
1: PWM mode2, three-phase modulation
LED ten’s digit: PWM low speed carrier
limit
0: Low speed carrier limit, carrier limit
mode 1
1: Low speed carrier limit, carrier limit
mode 2
2: Low speed carrier no-limit
0x01
◎
P09.47
Zero Frequency
Output Selection
0: No voltage output
1: Voltage output
2: Current output according to the stop
DC braking
0
○
P09.48
Action after
Accumulative
Power-On and Run
Time Reached
0: Output terminals action, error alarm
1: Output terminals action, no error alarm
0
○
P09.49
Motor
Power
Correction Coefficient
0.00%~200.0%
100.0%
○
P09.50
User-defined
Fault
Selection
LED unit’s digit
0: Disabled run after fault
1: Jog running after fault
LED ten’s digit
0: Coast to stop
1: Decelerate to stop
0x00
○
P09.55
Jog Preferred
Selection
0: Enabled
1: Disabled
0
○
P09.56
Auto-start Selection
after Manual Reset
0: Disabled
1: Enabled
0
○
P09.57
Stop brake
Frequency
0.00Hz~50.00Hz
1.50Hz
○
P09.58
Stop brake Time
0.0s~60.0s
2.0s
○
P09.59
A & B Frequency Fine
Tuning Superposition
Selection
LED unit’s digit:
0: A frequency allows for superposition
fine tuning frequency
1: A frequency prohibit superposition fine
0x00
○