VD300 Series Inverter User Manual
Parameter Description
- 153 -
P13.08
Inverter or Motor
Overload/Offload
Warning Selection
0x000~0x131
Led unit’s digit:
0: Motor overload / offload alarm, relative
to the rated current of the motor
1: Inverter overload / offload alarm,
relative to the rated current of inverter
Led ten’s digit:
0: Inverter continues to work after
overload / offload warning
1: Inverter continues to work after offload
alarm and stop to run after overload fault
2: Inverter continues to work after
overload alarm and stop to run after
offload fault
3: Inverter stops after offload / overload
fault
Led hundred’s digit:
0: Detection all the time
1: Detection in the constant speed run
0x000
○
The parameter is used to whether to selecting inverter pre-alarm function or motor pre-alarm function
etc. Such as pre-alarm, detection method and the disposal method after pre-alarming.
P13.09
Output Over-current
Detection
Value
0.0%: No detection
0.1%~300.0%
0.0%
○
P13.10
Output Over-current
Detection Time
0.0s~100.0s
0.0s
○
P13.11
Output Over-current
Action
0: Terminal output
1: Terminal output, alarm Er016
2: Terminal output, alarm Er016 when
constant speed run
3: Terminal output only in the constant
speed run
0
○
This group of function code is used to set detecting motor output current, output current over limit
detection delay time, DO action and inverter to detection result whether do the fault handling etc. If
choose error alarming then inverter will stop run. As below diagram: