Parameter Description
VD300 Series Inverter User Manual
- 140 -
again, priority jog run signal, otherwise, the first received signal.
P09.56
Auto-start Selection
after Manual Reset
0: Disabled
1: Enabled
0
○
Manual reset from the start allows the inverter in the running due to the failure signal to stop, manual
reset the fault, inverter will start again.
P09.57
Stop brake Frequency
0.00Hz~50.00Hz
1.50Hz
○
P09.58
Stop brake Time
0.0s~60.0s
2.0s
○
This set of function code used in braking output timing code. When the output frequency is lower than
P09.57 (stop braking frequency) set frequency, the function of DO 33 (braking timing output) outputs
ON signal, and continuous P09.58 (stop braking time) the set time.
P09.59
A & B Frequency Fine
Tuning Superposition
Selection
LED unit’s digit:
0: A frequency allows for superposition
fine tuning frequency
1: A frequency prohibit superposition fine
tuning frequency
LED ten’s digit:
0: B frequency allows for superposition
fine tuning frequency
1: B frequency prohibit superposition fine
tuning frequency
0x00
○
By this parameter to select the up/down fine tuning frequency is superimposed to the A or B of the
given frequency above.