Mechanical and Electrical Installation
VD300 Series Inverter User Manual
- 32 -
DO1-COM
Digital output 1
1. Optical coupling isolation, dual polarity
open collector output;
2. Pull-up voltage range: 5V~24V (pull-up
resistance range: 0.48kΩ~10kΩ);
3. Output current range: 2mA~50mA.
Digital Output
HDO1-COM
Rapid
pulse
input terminal
1. When used as general digital output, same
function as DO1;
2. Can be combined with the OPEN terminal
as bipolar high speed pulse output terminals,
max output frequency is 100kHz;
3. Pull-up voltage range: 5V-24V(pull-up
resistance range: 0.48kΩ~10kΩ).
4. Output current range: 2mA~50mA
T1/A-T1/B
Relay T1
normally
closed terminal
T1/A-T1/C
Relay T1
normally
open terminal
Relay Output
T2/A-T2/C
Relay T2
normally
open terminal
Contact driving capacity:
AC250V, 3A, DC 30V, 5A
Ground
PE
Shield cable
ground terminal
1. Used to control cable shield grounding,
when the interference is big on site or control
cable is too long, the PE should be well
grounded to reduce EMC affect.
2. PE terminal is not allowed to connect with
power N line, otherwise will damaged the
inverter
3.7.3 Jumper Switchover Function Description
Table 3-8 Jumper switchover function description
Jumper
Switchover
Code
Jumper
Selection
Function
A terminal
When jump cap plug connect to A, AO1 terminal select
DC0/4mA-20mA current signal output
J3
V terminal
When jump cap plug connect to V, AO1 terminal select
DC0V-10V voltage signal output
A terminal
When jump cap plug connect to A, AO2 terminal select
DC0/4mA-20mA current signal output
J4
V terminal
When jump cap plug connect to V, AO2 terminal select
DC0V-10V voltage signal output
J5
A terminal
When jump cap plug connect to A, AI2 terminal select
DC0/4mA-20mA current signal input