P00.06
Frequency output
lower limit after
superposition
-100%~100%
(100% corresponding to P00.07)
0.0%
◎
P00.06 is used to set the frequency output lower limit after superposition. The value is less than or
equal to the upper limit frequency, when the set frequency is lower than the frequency output lower
limit after superposition, then operation by lower limit frequency.
P00.07
Maximum Output
Frequency
P00.09~650.00Hz
50.00Hz
◎
Max frequency is the reference of all frequency relative quantity, as pulse input, analog terminal, MS
speed etc. Each of the percentage is relative to the max output frequency, such as analog input 10V,
change into 100%, corresponding (100%xP00.07) Hz.
Note: Output frequency of all operation will not exceed max output frequency.
P00.09
Running Frequency
Upper Limit Digital
Setting
P00.10~P00.07
50.00Hz
○
P00.10
Running Frequency
Lower Limit Digital
Setting
0.00Hz~P00.09
0.00Hz
○
P00.09 is used to set the upper limit of the running frequency. The value is less or equal to max output
frequency, when the set frequency is higher than the frequency upper limit then it runs with frequency
upper limit.
P00.10 is used to set the lower limit of the running frequency. The value is less or equal to upper limit
frequency, when the set frequency is lower than the frequency lower limit and the frequency lower
limit is greater than 0, the value set by the P01.20 to determine the operation mode of the inverter.
P00.11
Keypad Set
Frequency
0.00Hz~P00.07 (max output frequency)
50.00Hz
○
When A or B frequency command channel select function code P00.11 setup, this function code value
used as its channel frequency command directly.
P00.12
MS Speed
Command Stage 0
Command Source
0: Function code P11.00
1: Function code P00.11
2: AI1
3: AI2
4: AI3 (extension card)
5: High speed pulse
6: PID control set
7: Keypad potentiometer
0
◎
Selecting MS speed command stage 0 command source, can be set by function code P11.00, also by
analog preset to realize flexible adjusting. Refer to P11 MS speed parameter.
P00.14
Acceleration Time 0
0.0s~3600.0s
Model
depende
nt
○
P00.15
Deceleration Time
0
0.0s~3600.0s
Model
depende
nt
○
Acceleration/deceleration time means time needed if the inverter acceleration/deceleration from