VD300 Series Inverter User Manual
Parameter Description
- 105 -
6.6 P05 Input Terminals Function Parameter Group
P05.00
Terminal Control Running
Mode
0: Two-line mode 1
1: Two-line mode 2
2: Three-line mode 1
3: Three-line mode 2
4: Alternate control
0
◎
This parameter defines five different modes of controlling the operation of the inverter via the external
terminals
1: Two-line mode 1: This mode is the most commonly used two-line mode. The forward / reverse
rotation of the motor is decided by the commands of Dix, DIy terminals; when Dix and DIy are
effective, the inverter to keep the first effective terminal determined direction. The terminal function
set as below:
Terminal
Set Value
Description
Dix
1
Forward run
DIy
2
Reverse run
DIx, DIy is DI1~DI5, HDI1 Multi-function digital input terminals, electric level enabled.
Fig 6.6-1 Schematic diagram of two line mode 1
Two-line run mode 2: When this mode is adopted, DIx is enabled terminal. The direction is
determined by the status of DIy. Terminal function set as below.
Terminal
Set Value
Description
DIx
1
Running
DIy
2
(FWD/REV)
DIx, DIy is DI1~DI5, HDI1 Multi-function digital input terminals, electric level enabled.
Fig 6.6-2 Schematic diagram of two line mode 2
Three-line control mode 1: In this mode, Dln is enabled terminal, and the direction is controlled by DIx,
DIy respectively.