Parameter Description
VD300 Series Inverter User Manual
- 156 -
P13.19
Phase Loss Protection
0x00~0x11
Led unit’s digit:
0: Input phase loss protection disabled
1: Input phase loss protection enabled
Led ten’s digit:
0: Output phase loss protection disabled
1: Output phase loss protection enabled
Model
Dependent
○
The above parameter is used to select whether to provide protection for Input or output phase failure.
Only the VD series inverter of G model with over 11kW can have input phase loss protection function.
P13.20
Frequency Reduction
Function Selection when
an Instantaneous Power
Failure
0: Disabled
1: Enabled
0
○
P13.21
Frequency Reduction
Mode Selection when an
Instantaneous Power
Failure
0~1
0
○
P13.22
Frequency Decrease
Rate when an
Instantaneous Power
Failure
(P13.21=0 Enabled)
0.00Hz/s~50.00Hz/s
10.00Hz/s
○
P13.23
Deceleration Time when
an Instantaneous Power
Failure
(P13.21=1 Enabled)
0.0s~600.0s
5.0s
○
380VAC corresponding:
420.0VDC
P13.24
Estimate Voltage when
an Instantaneous Power
Failure
200.0VDC~600.0VDC
220VAC corresponding:
240.0VDC
○
This function means that when instant power failure or voltage suddenly drop, inverter output speed
will decrease and load feedback energy will compensate to drop of inverter DC bus voltage, in order
to keep inverter run and avoid under voltage error caused stopping.
P13.20 is used in selecting protection function in instantaneous power failure, P13.21 is used in
frequency reduction mode selection when an instantaneous power: 0 is frequency decrease
according to P13.22 frequency decrease rate. When bus voltage is low or instantaneous power failure
and P13.20=1, then inverter output frequency will judge and interfere inverter output frequency
according to P13.21 selection mode and P13.22 set value, will normal run until bus voltage recovery.
P13.25
Short-circuit to Ground
Upon Power-on
0: Enabled
1: Disabled
0
○
To check if motor is short circuit to ground when inverter powered on, if selecting detection enabled,
inverter output terminal U, V, W has voltage output after powered on for a short period, it is used to
check if motor is short circuit to ground or not.