VD300 Series Inverter User Manual
Function Parameter Table
- 81 -
P21.13
Suppression
Oscillation Threshold
of Motor 2
0.00Hz~P00.07 (Maximum frequency)
30.00Hz
○
P21.14
Motor 2 Voltage
Setting Channel
Selection
0: Function code P21.15
1: AI1
2: AI2
3: AI3 (extension card)
4: HS Pulse input
5: PID control setting
6: Communication setting
0
◎
P21.15
Motor 2 Keypad
Setting Voltage Value
0.0%~100.0%
100.0%
○
P21.16
Motor 2 Voltage
Increasing Time
0.0s~3600.0s
5.0s
○
P21.17
Motor 2 Voltage
Decreasing Time
0.0s~3600.0s
5.0s
○
P21.18
Motor 2 Maximum
Output Voltage
P21.19~100.0%
(Rated voltage of motor)
100.0%
◎
P21.19
Motor 2 Minimum
Output Voltage
0.0%~P21.18
(Rated voltage of motor)
0.0%
◎
P21.20
Motor 2 V/F
Control
Weak Magnetic
Coefficient
1.00~1.30
1.00
○
P21.21
Energy-saving
Running Selection of
Motor 2
0: Disabled
1: Enabled
0
◎
P28 Condition Monitoring Parameters Group
Function
Code
Parameter Name
Setting Range
Factory
Default Value
Property
P28.00
Running Frequency
0.01Hz
●
P28.01
Set Frequency
0.01Hz
●
P28.02
Slope Given
Frequency
0.01Hz
●
P28.03
Bus Voltage
0.1V
●
P28.04
Output Voltage
1V
●
P28.05
Output Current
0.1A
●
P28.06
Torque Current
0.1A
●
P28.07
Exciting Current
0.1A
●