Parameter Description
VD300 Series Inverter User Manual
- 102 -
6.5 P04 motor 1 V/F Control Parameters Group
P04.00
Motor 1V/F Curve Setting
0: Straight line V/F curve
1: Multi-stage V/F curve
2: 1.3#power low torque V/F curve
3: 1.7#power low torque V/F curve
4: 2.0#power low torque V/F curve
5: V/F complete separation
6: V/F half separation
0
◎
If P00.00 set as 0(V/F control mode), then V/F type is set by P04.00. User can select appropriate V/F
curve type according to loading type. If loading is wind pump water pump etc., generally select square
V/F curve, 2.0 # power. As below diagram:
Fig 6.5-1 Schematic diagram for parabolic type
P04.02
Multi-Stage V/F
Frequency Point 1
0.00Hz~P04.04
0.00Hz
○
P04.03
MS V/F Voltage Point 1
0.0%~110.0% (rated motor 1 voltage)
0.0%
○
P04.04
MS V/F Frequency Point
2
P04.02~P04.06
0.00Hz
○
P04.05
MS V/F Voltage Point 2
0.0%~110.0% (rated motor 1 voltage)
0.0%
○
P04.06
MS V/F Frequency Point
3
P04.04~P00.07 (max output frequency)
0.00Hz
○
P04.07
MS V/F Voltage Point 3
0.0%~110.0% (rated motor 1 voltage)
0.0%
○
When P04.00 set as 1(MS V/F), each stage frequency and voltage can be set by above function code,
details as below diagram. The 1
st
point is 0.00Hz, output voltage is manual torque boost (P04.09)
corresponding voltage. The 5
th
point is rate frequency, output voltage is rate voltage. Other voltage is
formed by 5points linear interpolation. MS V/F is used in special application which users has output
voltage requirement, or be used in solving some frequency point with resonance phenomena.