VD300 Series Inverter User Manual
Parameter Description
- 157 -
P13.26
Fault Output Terminals
Action Selection during
Fault
0x00~0x11
Led unit’s digit:
0: Action upon under-voltage error
1: No action upon under-voltage error
Led ten’s digit:
0: Action during auto reset
1: No action during auto reset
0x00
○
Used to select fault output terminals in the under-voltage and fault automatic reset action.
P13.27
Fault Auto Reset Times
0~20
0
○
When the inverter selects fault auto reset, it is used to set the times of auto reset. If fault times
exceeded this parameter value, the inverter will keep error status.
P13.28
Time Interval of Fault
Auto Reset
0.1s~3600.0s
1.0s
○
The parameter is used to set the interval time from inverter error alarming to auto reset error. If
inverter occurred error within the interval time then inverter will not reset and give alarming.
P13.29
Fan Start Mode
0: Automatic control
1: Fan running all the time
0
○
Used to select a cooling fan mode of action, choosing to 0, the run state of the inverter in the fan
operation, stop state if the radiator temperature is above 40 degrees fan operation, stop condition
radiator temperature below 40 degrees fan doesn't work. This mode can greatly improve the service
life of the cooling fan.
Choose to 1, the fan has been run after the inverter to electricity.
P13.30
Automatic Frequency
Reduction Selection
when Voltage Reduction
0: Disabled
1: Enabled
0
○
380VAC corresponding:
513.0VDC
P13.31
Automatic Frequency
Reduction Point when
Voltage Reduction
200.0VDC~600.0VDC
220VAC corresponding:
297.0VDC
○
When the voltage drop but the automatic frequency reduction function is effective,
the inverter can
guarantee the output rated torque when the grid
voltage drops to the voltage automatic frequency
drop point.
P13.32
Emergency Stop Time
0.0s~3600.0s
5.0s
○
Combination with DI function 24 emergency stop time, decided to stop time.