Function Parameter Table
VD300 Series Inverter User Manual
- 46 -
P01.21
Dormant Recover
Delay Time
0.0s~3600.0s
(corresponding P01.20=2 is effective)
0.0s
О
P01.22
Power-on Terminal
Running Protection
Selection
0: Terminal operation command is
disabled when power on
1: Terminal operation command is
enabled when power on
0
○
P01.23
Restart Selection
Upon Power Failure
0: Disabled restart
1: Allow restart
0
○
P01.24
Waiting Time of
Restart Upon Power
Failure
0.0s~3600.0s
(corresponding P01.23=1 is effective)
1.0s
○
P01.25
Start Delay Time
0.0s~60.0s
0.0s
◎
P01.26
Acceleration/Decelera
tion Mode Selection
0: Straight-line type
1: S curve (reserved)
0
◎
P01.27
Ratio of S Curve Start
Segment
0.0%~ (100.0%-P01.28) (relate to
Acceleration/deceleration time)
30.0%
●
P01.28
Ratio of The S Curve
End Segment
0.0%~ (100.0%-P01.27) (relate to
acceleration/deceleration time)
30.0%
●
P01.29
Rotation Speed
Tracking Mode
Selection
Unit’s digit of LED : tracking direction
selection
0: According to the actual detection
direction
1: According to the run direction before
stop
Ten’s digit of LED: zero speed exciting
selection
0: No exciting
1: Exciting
0x00
○
P01.30
Delay Time of
Rotation Speed
Tracking
0~2000ms
500
○
P01.31
Voltage Rise Rate of
Rotation Speed
Tracking
0~1000
100
○
P02 Motor 1 Parameter Group
Function
Code
Parameter Name
Setting Range
Factory
Default
Value
Property
P02.00
Motor 1 Type
0: Asynchronous motor
0
●
P02.01
Rated Motor 1 Power
0.4kW~1000.0kW
Model
dependent
◎