VD300 Series Inverter User Manual
Parameter Description
- 155 -
The above parameter is used to open inverter energy consumption braking voltage threshold, when
inverter configured braking unit.
P13.16
Current Limit Selection
0x00~0x11
Led unit’s digit: current limiting action
selection
0: Disabled current limiting action
1: Enabled for current limiting action
Led ten’s digit: hardware current limiting
overload alarm selection
0: Hardware current limiting overload
alarm enabled
1: Hardware current limiting overload
alarm disabled
0x01
◎
G type: 160.0%
P13.17
Automatic Current Limit
Level
50.0%~200.0%
P type: 120.0%
◎
P13.18
Frequency Decrease
Rate when Current
Limiting
0.00Hz/s ~50.00Hz/s
10.00Hz/s
◎
Overcurrent stall is similar to overvoltage stall, when inverter is in starting acceleration process, then
inverter output frequency stop acceleration and keep current running frequency, waiting until output
current lower than stall upper limit then starting acceleration. As Fig 6.12-6 showed.
If inverter in constant speed operation, load jump and result in inverter output current exceeding
overcurrent stall upper limit, the output frequency of inverter will decrease as P13.18 set and keep
decreasing until inverter output current less than P13.17 setting threshold value. As Fig 6.12-6 in
constant speed operation:
Fig 6.12-6 Diagram for over-current stall protection