Parameter Description
VD300 Series Inverter User Manual
- 138 -
P09.42
^/V Key Integration Rate
0.01s~10.0s
1.0s
○
If select v/^ key integration function enabled, the parameter is used to set v/^ key integration rate
value, the bigger the value is, the smaller the change rate is.
P09.43
UP/DOWN Terminals
Control Set
0x000~0x221
LED unit’s digit: frequency control
selection
0: UP/DOWN terminals setting enabled
1: UP/DOWN terminals setting disabled
LED ten’s digit: Frequency control
selection
0: Only enabled when P00.02=1or
P00.03=1
1: All frequency mode are enabled
2: When the multi-step speed are
priority, it is disabled to the multi-step
speed
LED hundred’s digit: action selection
when stop
0: Setting enabled
1: Enabled in run , clear after stop
2: Enabled in run , clear upon receiving
stop command
0x000
○
Used to set terminal UP/DOWN function selection
P09.44
UP/DOWN Terminals
Frequency Change Rate
0.01Hz/s ~50.0Hz/s
1.00Hz/s
○
If choosing terminals UP/DOWN function, set the parameters used in the terminal UP/DOWN the size
of the function change rate, the greater the value, the greater the rate of change.
P09.45
Frequency Setting at
Power Loss Action
Selection
0x000~0x111
LED unit’s digit: action selection when
digital adjustment frequency with power
off
0: Save when power off
1: Clear when power off
LED ten’s digit: action selection when
Modbus setting frequency power off
0: Save when power off
1: Clear when power off
LED hundred’s digit: action selection
when other Communication set
frequency power off
0: Save when power off
1: Clear when power off
0x000
○
Used to set when the inverter power electricity again, select whether frequency is memory or storage
when power failure.