Parameter Description
VD300 Series Inverter User Manual
- 116 -
P05.59
DI8 Terminals Open
Delay Time
0.0s~6000.0s
0.0s
○
P05.60
DI9 Terminals Close
Delay Time
0.0s~6000.0s
0.0s
○
P05.61
DI9 Terminals Open
Delay Time
0.0s~6000.0s
0.0s
○
The group function code is used to set the delay time of inverter disposing input signal when the input
terminal connecting and disconnecting. HDI1 channel input function is Enabled only when switchover
input function namely P05.10 = 1 delay effective. As following figure:
Fig 6.6-8 DI connection delay and disconnection delay diagram
P05.62
Virtual Input Terminal
Setting Selection
0: Disabled
1: Communication setting
0
○
This function code is used to set the input terminals in the communication control, whether or not to
use communication virtual terminal to control converter. Please refer to the communication protocol in
detail. Note: when the input terminals use communication control, can only use all communication
virtual terminal control mode.
P05.63
Travel Switch Lock Time
0.0s~60.0s
1.0s
○
For terminal control operation mode 5 (back and forth control), please refer to the detail specification
of round trip control mode.