Parameter Description
VD300 Series Inverter User Manual
- 152 -
Inverter or motor overload pre-alarming detection time: DO output overload pre-alarm signal, when
overload pre-alarm occurred and greater than overload pre-alarm detection time. As below diagram:
P13.04
Time
DO
Output
Time
Output current
P13.05
DO
Output
FIG 6.12-2 Detection of overload pre-alarm
P13.06
Inverter or Motor Offload
Warning Detection level
0%~P13.04
50%
○
P13.07
Inverter or Motor Offload
Warning Detection Time
0.0s~3600.0s
1.0s
○
Inverter or motor offload pre-alarm detection level: before inverter or motor offload error protection,
through DO send a pre-alarm signal to control system. The pre-alarm coefficient is to decide what
time to pre-alarm before inverter or motor offload protection. The bigger the value is, the bigger the
pre-alarm advanced quantity is.
Inverter or motor offload pre-alarm detection time: DO output offload pre-alarm signal, when offload
pre-alarm occurred and greater than offload pre-alarm detection time. As below diagram:
Fig 6.12-3 Offload pre-alarm detection
Содержание VD300 Series
Страница 2: ......