VD300 Series Inverter User Manual
Parameter Description
- 143 -
Motor rotating
speed(RPM ON)
0x0020
Inverter overload
percentage(% ON)
0x0020
Output power(% ON)
0x0040
Linear speed
0x0040
Output torque(% ON)
0x0080
Excitation current(A
ON)
0x0080
PID setting value(%
flash)
0x0100
Torque current(A ON)
0x0100
PID feedback value(%
ON)
0x0200
AC line-in current (A
ON)
0x0200
Input terminal state
0x0400
Output terminal state
0x0800
Torque setting
value(% ON)
0x1000
Pulse counting value
0x2000
PLC & MC speed
present stage
0x4000
Slope frequency
setting value(Hz ON)
0x8000
Example 1: for example while runtime only need to display motor rotating speed, other parameters do
not need to be displayed.
Motor rotating speed display is at lower bit P10.03, corresponding hexadecimal 0x0020, run display
high bit parameter is 0, then set P10.03=0*0020, P10.04=0x0000.
Example 2: such as constant pressure water supply system only need to display the real-time
pressure value, which shows the inverter PID feedback, other parameters do not need to display. PID
feedback in shown at low bit P10.03 which corresponding hexadecimal 0x0200, run shown high bit is
all 0, and set P10.03 = 0 x0200, P10.04 x0000 = 0.
Note: if need to display the pressure units at run time, it must be properly set P08.05 parameters.
Example 3: such as the need to display the operation of the inverter frequency and the output current
and other parameters are not displayed. Inverter output frequency is in the run showed low P10.03,
corresponding to the hex 0 x0001; Inverter output current is in the run showed low P10.03,
corresponding to the hex 0 x0010; This set P10.03 = 0 x0001 + 0 x0010 = 0 x0011, P10.04 x0000 = 0.
At this time to shift by pressing the shift key until the operation of the need to look at the inverter
frequency and the output current.
P10.05
Display Stop
0x0000~0xFFFF
BIT0: Set frequency (Hz flash)
BIT1: Bus voltage (V light on)
BIT2: State of input terminals
BIT3: State of output terminals
BIT4: PID setting value (% flash)
BIT5: PID Feedback value (% on)
BIT6: Torque setting value (% on)
BIT7: Analog AI1 value (V light on)
BIT8: Analog
AI2 value (V light on)
BIT9: Analog
AI3 value
0x0003
○