Parameter Description
VD300 Series Inverter User Manual
- 118 -
ready running
the inverter not detected any failure information, the inverter in the
running, output ON signal.
8
Overload
pre-warning
Before overload protection, according to the overload forecasting
warning threshold value to judge, after more than forecasting
warning threshold output ON signal. Parameter set refer to the
function code P13.04, P13.05, P13.08.
9
Off load pre-warning
Before offload protection, according to the overload forecasting
warning threshold value to judge, after more than forecasting
warning threshold output ON signal. Parameter set refer to the
function code P13.06, P13.07, P13.08.
10
Frequency level
detection FDT1
output
Please refer to the function code P09.10, P09.11 specification
11
Frequency level
detection FDT2
output
Please refer to the function code P09.12, P09.13 specification
12
Zero speed running
1 (have no output
when stop)
When frequency inverter is running and the output frequency is 0,
the output ON signal. When inverter is in a state of downtime, the
signal is OFF.
13
Frequency reached
When the output frequency of inverter into the set frequency
detection range, output ON signal, see the function code P0.09.
14
Frequency upper
limit reached
When operation frequency reach to the upper limit frequency,
output ON signal.
15
Frequency lower
limit reached
When operation frequency reach to the lower limit frequency,
output ON signal. When inverter is in a state of downtime, the
signal is OFF.
16
Set count value
reached
When the count reach to the set value of P09.27, the output ON
signal. Counting function reference function group P09.
17
Designated count
value reached
When the count reach to the set value of P09.28, the output ON
signal.
18
Simple PLC stage
complete
After finished each stage of a PLC, output a pulse signal whit
250ms width.
19
Simple PLC circulate
complete
After finished a cycle of a PLC, output a pulse signal whit 250ms
width.
20
External fault
enabled
When external fault signal.
21
Accumulative
running time reached
When frequency inverter in the total run time more than the setting
time of P09.30, output ON signal.
22
Accumulative
power-on time
reached
When frequency inverter in the total on power time more than the
setting time of P09.31, output ON signal.
23
Current running time
reached
When frequency inverter run time more than the setting time of
P09.32, output ON signal.
24
Current power-on
time reached
When frequency inverter on power time more than the setting time
of P09.33 output ON signal.