Parameter Description
VD300 Series Inverter User Manual
- 144 -
(extension card) (V light on)
BIT10: High speed pulse HDI frequency
BIT11: PLC and present stage of multi
stage speed
BIT12: Pulse counting value
BIT13: User-defined speed 1
(setting value)
BIT14: User-defined speed 2
(setting value)
BIT15: Reserved
Inverter in stop state, the parameters according to the function code, which is a 16 bit binary number,
if one is 1, then the corresponding parameters can be during downtime, can see through the shift key.
If the bit is 0, then the corresponding parameters will not be displayed. The lower bits, the higher the
display priority is. Please refer to the operation display parameters detailed setting method.
Stop display parameter P10.05 corresponding table
Corresponding display parameter
Hexadecimal
Set frequency (Hz on)
0x0001
Bus voltage (V on)
0x0002
Input terminal state
0x0004
Output terminal state
0x0008
PID given value (% flash)
0x0010
PID feedback value (% on)
0x0020
Torque set value (% on)
0x0040
Analog AI1 value (V on)
0x0080
Analog AI2 value (V on)
0x0100
Analog AI3 value (extended card) (V on)
0x0200
HS pulse HDI frequency
0x0400
PLC & MS speed present stage
0x0800
Pulse count value
0x1000
User-defined speed 1 (Set value)
0x2000
User-defined speed 2 (Set value)
0x4000
P10.06
User-defined Speed 1
Coefficient
0.00~60.00
User-defined speed 1= Running
frequency*P10.06
1.00
○
Used for correct the display the coefficient of user-defined speed 1. After user change the
user-defined speed 1 coefficient, inverter LED displayed actual frequency = frequency * P10.06.