![Thytronic XMR-A 4l+1A Скачать руководство пользователя страница 78](http://html1.mh-extra.com/html/thytronic/xmr-a-4l-1a/xmr-a-4l-1a_manual_1113984078.webp)
78
FUNCTION CHARACTERISTICS
The relay residual rated voltage
U
En
must be indifferently estimated by means of the following ge-
neral formula:
U
En
= √3 ·
U
ng
/
K
VT
= √3 · 6000 / (√3 · 60) = 100 V
or by means the following streamlined formula:
U
En
= 3 ·
U
ns
= 3 · 100 / 3 = 100 V
Case B
The relay residual rated voltage
U
En
must be estimated by means of the following general formula:
If a VT with primary rated voltage equal to the grid voltage divided by √3 is connected from star neu-
tral to ground, the following streamlined calculus may be used:
U
En
= VT secondary rated voltage [V]
Example B1
The relay residual rated voltage
U
En
may be estimated by means of the following formula:
U
En
= (
U
ng
/√3) /
K
VT
= (10000 /√3) / (110/ √3) = 91 V
Example B2
The relay residual rated voltage
U
En
may be estimated by means of the following general formula:
U
En
= (
U
ng
/√3) /
K
VT
= (6000 /√3) / (60/ √3) = 100 V
Case C
The relay residual calculated rated voltage
U
ECn
is estimated automatically by means of the formula:
U
ECn
= √3∙
U
n
Example C1
For the example 2
U
n
= 100 V.
U
ECn
is estimated automatically by means of the formula:
U
ECn
=
U
n
∙ √3
= 100 ∙ √3
= 173 V
VT ratio
K
VT
Grid nominal voltage
U
ng
where the VTs [V] / √3 are connected
U
En
=
EsB1-UEn.ai
K
VT
=
/
V
V
11000 3
3
100
= 110 /
K
VT
=
/
V
V
11000 3
3
100
= 110 /
Grid nominal voltage
U
ng
= 10 kV
Ratio of VT connected from star neutral to ground:
U
ng
= 10 kV
U
En
XMR-x
EsB2-UEn.ai
K
VT
=
/
V
V
6000
3
3
100
= 60 /
K
VT
=
/
V
V
6000
3
3
100
= 60 /
Grid rated voltage
U
ng
= 6kV
Ratio of VT connected from star neutral to ground:
U
ng
= 6 kV
U
En
XMR-x
U
ECn
= 173 V
U
n
= 100 V
Es4-UEn.ai
K
VT
=
/
/
V
V
6000
3
100 3
= 60
/
/
V
V
6000
3
100 3
= 60
Grid rated voltage
U
ng
= 6 kV
Ratio of line VTs
K
VT
=
U
np
/
U
ns
=
U
ng
= 6 kV