![Thytronic XMR-A 4l+1A Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/thytronic/xmr-a-4l-1a/xmr-a-4l-1a_manual_1113984046.webp)
46
TECHNICAL DATA
First threshold (
I
d
>)
0.05...2.00
I
nref
(step 0.01
I
nref
)
First stretch slope percentage (
K1)
10...50%
(step 1 %)
Second branch slope percentage (
K2)
25...100%
(step 1 %)
Second branch intersection with vertical axis (
Q) 0.00...3.00
I
nref
(step 0.01
I
nref
)
First threshold
operating time
I
d
>
(
t
d
>)
0.04
s
I
d
>>
Element (87M-87G-87T)
Second threshold (
I
d
>>)
0.50...30.00
I
nref
(step 1.00
I
nref
)
Second threshold
operating time
I
d
>>
(
t
d
>>)
0.03
s
—
Lock-out - 86
Contact
quantity 4
Rated current
8 A
Rated voltage/max switching voltage
250 Vac/400 Vac
Short duration current (0,5 s)
30 A
Make 1000
W/VA
Minimum switching load
300 mW (5 V/ 5 mA)
Operating time:
Make contacts
< 10 ms
Break contacts
< 10 ms
—
Vector jump
d
phi
> Element
Definite time
First threshold definite time (
d
phi
>
def
)
1...20 ° (step 1 °)
Operating mode (
d
phi
>
mode
)
Module/Positive/Negative
Operating time (
t
phi
>)
≤0.05 s
Enabling threshold
0.20
U
n
Minimum time to voltage presence (
t
nUf
<
def
)
0.00...20.0
s
0.05...9.99 s (step 0.01 s)
10.0...20.0 s (step 0.1 s)
—
Breaker failure - BF (Side L and Side H)
Phase current threshold (
I
BF(L)
>) 0.05...1.00
I
n (L)
(step 0.01
I
n (L)
)
Residual current threshold (
I
EBF (L)
>)
0.01...2.00
I
n (L)
(step 0.01
I
En (L)
)
Time delay(
t
BF (L)
)
0.06...10.00 s (step 0.01 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Pickup accuracy (
I
BF (L)
>) ±
0.5% with 0.1
I
n (L)
±
0.2% with 1
I
n (L)
Pickup accuracy (
I
EBF (L)
>)
±
1% with 0.01
I
En (L)
±
0.3% with 1
I
En (L)
Operate time accuracy
5% ±
10 ms
Phase current threshold (
I
BF(H)
>) 0.05...1.00
I
n (H)
(step 0.01
I
n (H)
)
Residual current threshold (
I
EBF (H)
>)
0.01...2.00
I
n (H)
(step 0.01
I
En (H)
)
Time delay(
t
BF (H)
)
0.06...10.00 s (step 0.01 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Pickup accuracy (
I
BF (H)
>) ±
0.5% with 0.1
I
n (H)
±
0.2% with 1
I
n (H)
Pickup accuracy (
I
EBF (H)
>)
±
1% with 0.01
I
En (H)
±
0.3% with 1
I
En (H)
Operate time accuracy
5% ±
10 ms
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021