FUNCTION CHARACTERISTICS
327
The element can be enabled or disabled by setting
ON
or
OFF
the
State
parameter inside the
Set
\ Profile A (or B) \ Vector jump-dphi \ dphi> Element \ Definite time
menu.
The phase change only positive or only negative, as well as any variation (module) may be selected
by means of the
Mode dphi>
parameter inside the
Set \ Profile A (or B) \ Vector jump-dphi \
dphi> Element \ Setpoints
menu.
Breaker failure (BF)
dphi threshold can be associated to BF (H) and BF (L) protection by activating the relative parameter
in the matrices “Selection of function tripping for BF (H)” or “Selection of function tripping for BF (L)”
in relevant
BF
menus
1
:
• Set \ Profile A (or B) \ Breaker failure - BF side H
• Set \ Profile A (or B) \ Breaker failure - BF side L
Logical block (Block1)
If the
dphi>BLK1
enabling parameter is set to
ON
and a binary input is designed for logical block
(Block1), the protection is blocked off whenever the given input is active.
The trip timer is held in reset condition, so the operate time counting starts when the input block goes
down.
2
The enabling parameters are available inside the
Set \ Profile A (or B) \ Vector jump-dphi
\ dphi> Element \ Setpoints
menus, while the
Block1
function must be assigned to the selected
binary input inside the
Set \ Board 1(2) inputs \ Binary input IN1-1...(IN1-x)
menus.
Note 1 The common settings concerning the Breaker failure protection are adjustable inside the
Breaker Failure - BF
menu.
Note 2 The exhaustive treatment of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside
CONTROL AND MONITOR-
ING
section.
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021