![Thytronic XMR-A 4l+1A Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/thytronic/xmr-a-4l-1a/xmr-a-4l-1a_manual_1113984026.webp)
26
TECHNICAL DATA
Operate time accuracy
5% ±
10 ms
—
Directional reactive underpower 37Q
Common configurations:
CB-37Q enable (
CB-37Q
)
ON/OFF
CB-37Q delay (
t
ARM-Q<
)
0.07...300
s
0.07...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...300 s (step 1 s)
Soglia Q1<
Setpoints
Tripping direction (
Q
1
<
DIR
)
Q Forward/Q Reverse/Q Forward-Qeverse
Definite time
First threshold definite time (
Q1<
def
)
0.01...1.50
Q
n
Operating time (
t
Q
<)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Soglia Q2<
Setpoints
Tripping direction (
Q
2
<
DIR
)
Q Diretta/Q Inversa/Q Diretta-Inversa
Definite time
Second threshold definite time (
Q2<
def
)
0.01...1.50
Q
n
Operating time (
t
Q2
<
def
)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤
0.04 s
Dropout
ratio
1.03...1.05
Dropout time
≤
0.05 s
Overshoot time
0.04 s
Pickup
accuracy ±
3% with 0.01
Q
n
±
0.5% with 0.1
Q
n
Operate time accuracy
5% ±
10 ms
—
Loss of field - 40
Common configurations:
Operating mode
(
Mode 40
)
Motor/Generator
Undervoltage threshold (
U
SUP
<)
0.50...1.00
U
n
(risoluzione 0.01
U
n
)
40AL Alarm
Inclination angle
a
(
ALPHA40
AL
)
10...75° (step 1°)
Operating time (
t
40AL
)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
XC1-XD1 Element
Absolute center coordinate (X
C1
) 0.00...4.50
Z
nf
(step 0.01 Z
nf
)
Diameter (
X
D1
)
0.20...5.00
Z
nf
(step 0.01 Z
nf
)
Operating time (
t
XC1XD1
)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (
t
XC1XD1-RES
)
0.0...10.0 s (step 0.1 s)
XC2-XD2 Element
Absolute center coordinate (X
C2
) 0.00...4.50
Z
nf
(step 0.01 Z
nf
)
Diameter (
X
D2
)
0.20...5.00
Z
nf
(step 0.01 Z
nf
)
Operating time
(
t
XC2XD2
)
0.07...100.0
s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (
t
XC2XD2-RES
)
0.0...10.0 s
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot time
0.04 s
Pickup
accuracy ±
0.5% on current measures
±
0.5% on voltage measures
Operate time accuracy
5% ± 10 ms
—
Negative sequence overcurrent for Line/Transformer protection- 46LT
I
2
> Element
Curve type (
I
2
>
Curve
)
DEFINITE,
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI,
I
2
t, EM
CLP mode (
I
2CLP
>
Mode)
OFF/ON-Element blocking/ON-Change setting
CLP activation time (
t
2CLP>
) 0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021