FUNCTION CHARACTERISTICS
203
generator is connected to its own step-up transformer.
All elements can be enabled or disabled by setting
ON
or
OFF
the
State
parameters inside the
Set \
Profile A (or B) \ Voltage controlled-restraint overcurrent 51V \
I-I/U> Element
(
I-I/U>> Element) \ De-
finite time
menus.
The trip of first element may be inhibited by the start of the second element by setting
ON
the Disable
I-I/U> by start I-I/U>> (
I-I/U>disbyI-I/U>>
) parameter available inside the
Set \Profile A (or B) \
Voltage controlled-restraint overcurrent 51V \
I-I/U>> Element \ Setpoints
menu.
An adjustable reset time delay is provided for every threshold (
t
-I/U>RES
,
t
-I/U>>RES
), useful for coor-
dination with electromechanical relays, in order to improve sensitivity against swings between the
generator and the grid, or to reduce intermittent fault elimination times.
Both the protection elements are blocked off whenever the VT supervision function is active, so
that no unwanted trip can arise if any fault on the VTs secondary circuits (break, fuse trip, etc) are
detect;
[1]
the Block functions enable from 74VT parameter (
74VT-BK-EN
)
is available inside the
Set \ VT supervision -74VT
menu.
Breaker failure (BF)
Each thresholds (I-I/U>, I-I/U>>) can be associated to BF (H) and BF (L) protection by activating the
relative parameter in the matrices “Selection of function tripping for BF (H)” or “Selection of function
tripping for BF (L)” in relevant
BF
menus
[2]
:
• Set \ Profile A (or B) \ Breaker failure - BF side H
• Set \ Profile A (or B) \ Breaker failure - BF side L
Note 1 The exhaustive treatment of the VT supervision function may be found inside the
CONTROL AND MONITORING
section.
Note 2 The common settings concerning the Breaker failure protection are adjustable inside the
Breaker Failure - BF
menu.
51V-VR_char.ai
First threshold
Second threshold
U
-I/U-2
<
U
-I/U-1
<
U
-I/U-2
<
U
-I/U-1
<
I
-I/U
>>
I
-I/U
>
K
I
-I/U
>>
K
I
-I/U
>
Voltage
Voltage
Current threshold
Current threshold
Voltage controlled thresholds
General logic diagram of the voltage restraint-voltage controlled overcurrent elements - 51V
Block1
Block1
U
12
,
U
2 3
,
U
31
I
L1
,
I
L 2
,
I
L 3
U
12
,
U
2 3
,
U
31
I
L1
,
I
L 2
,
I
L 3
Block 2
Block 2
Block3
Block1
Block 2
Block3
Block1
Block 2
State
I
-I/U>>def
U
-I/U
<
U
-I/U-1
<
U
-I/U-2
<
K
t
-I/U>>def
t
-I/U>>
RES
State
I
-I/U>def
I
-I/U
> Trip
I
-I/U
> Star t
I
-I/U
>> Trip
I
-I/U
>> Star t
I
-I/U
>> Star t
t
-I/U>def
t
-I/U>
RES
Mode 51V>
Voltage controlled
Voltage restraint
I
-I/U
> inhibition
I-I/U>> Element
I-I/U> Element
Common configuration
ON=inhibit
&
I
-I/U
> disby
I
-I/U
>>
START I-I/U>
TRIP I-I/U>
RESET
INPUT
Timers-F51V.ai
t
-I/U>RES
t
-I/U>def
t
-I/U>def
t
-I/U>RES
t
-I/U>RES
t
Voltage controlled-restraint overcurrent elements (51V) - Timers
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021