![Thytronic XMR-A 4l+1A Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/thytronic/xmr-a-4l-1a/xmr-a-4l-1a_manual_1113984045.webp)
TECHNICAL DATA
45
Definite time
Third threshold definite time (
f<<<
def
)
0.800...1.000
f
n
(step 0.001
f
n
)
Operating time (
t
f
<<<
def
)
0.05...100.0
s
0.05...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
f<<<< Element
Definite time
Fourth threshold definite time (
f<<<<
def
)
0.800...1.000
f
n
(step 0.001
f
n
)
Operating time (
t
f
<
def
)
0.05...100.0
s
0.05...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤
0.04 s
Dropout ratio
≤
1.002
Dropout time
≤
0.05 s
Overshoot time
0.04 s
Reference values
rest: setting value + 0.2 Hz
trip: setting value - 0.2 Hz
Pickup accuracy
±5 mHz with 0.02
U
n
, ±
2 mHz with 1
U
n
Operate time accuracy
5%
±
10 ms
—
Frequency rate of change (81R)
df> Element
Operating mode (
Mode-df>
)
Module/Positive/Negative
Definite time
First threshold definite time (
df
>
def
)
0.1...10.0 Hz/s (step 0.1 Hz/s)
Operating time (
tdf
>
def
)
0.00...100.0
s
0.00...0.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
df>> Element
Operating mode (
Mode-df>>
)
Module/Positive/Negative
Definite time
Second threshold definite time (
df
>>
def
)
0.1...10.0 Hz/s (step 0.1 Hz/s)
Operating time (
tdf
>>
def
) 0.00...100.0
s
0.00...0.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
df>>> Element
Operating mode (
Mode-df>>>
)
Module/Positive/Negative
Definite time
Third threshold definite time (
df
>>>
def
)
0.1...10.0 Hz/s (step 0.1 Hz/s)
Operating time (
tdf
>>>
def
) 0.00...100.0
s
0.00...0.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
df>>>> Element
Operating mode (
Mode-df>>>>
)
Module/Positive/Negative
Definite time
Fourth threshold definite time (
df
>>>>
def
)
0.1...10.0 Hz/s (step 0.1 Hz/s)
Operating time (
tdf
>>>>
def
)
0.00...100.0
s
0.00...0.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤
0.3 s with setting
d
f: 0.1...0.9 Hz/s
≤
0.2 s with setting
d
f: 1.0...4.9 Hz/s
≤
0.1 s with setting
d
f: 4.9...10.0 Hz/s
Dropout time
≤
0.05 s
Reference values
rest 0
d
f
trip
1.5
d
f
Pickup accuracy
±
20 mHz/s with setting
d
f: 0.1...0.9 Hz/s
±
50 mHz/s with setting
d
f: 1.0...4.9 Hz/s
±
200 mHz/s with setting
d
f: 4.9...10.0 Hz/s
Operate time accuracy
5% ± 20 ms
—
Differential - 87G-87M-87T
Harmonic restraint (87T)
87T Second harmonic restraint threshold (
2nd-REST>)
10...80%
I
d
(step 1%
I
d
)
87T Fifth harmonic restraint threshold (
5th-REST>) 10...80%
I
d
(step 1%
I
d
)
87T Harmonic restraint intentional reset time delay (
t
H-RES
)
0.00...10.00 s
(step 0.01 s)
87T Cross phase harmonic restraint enable (
C
ROSS
H-RES
)
ON/OFF
CT saturation detector (87M-87G-87T)
Saturation detector enable (
S
at-Det
)
ON/OFF
Saturation detector intentional reset time delay (
t
Sat-Det-RES
)
0.00...0.50 s
(step 0.01 s)
I
d
>
Element (87M-87G-87T)
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021