![Thytronic XMR-A 4l+1A Скачать руководство пользователя страница 109](http://html1.mh-extra.com/html/thytronic/xmr-a-4l-1a/xmr-a-4l-1a_manual_1113984109.webp)
FUNCTION CHARACTERISTICS
109
—
Directional reactive overpower - 32Q
Preface
The ractive power is calculated as:
Q
=
U
L1
I
L1
sin
f
L1
+
U
L2
I
L2
sin
f
L2
+
U
L3
I
L3
sin
f
L3
where:
• U
L1
,
U
L2
,
U
L3
are the fundamental components of the phase-to-neutral voltages
• I
L1
,
I
L2
,
I
L3
are the fundamental components of the phase currents
• f
L1
,
f
L2
,
f
L3
, are the displacement angles of phase currents
I
L1
,
I
L2
,
I
L3
respect to the phase voltages
U
L1
,
U
L2
,
U
L3
, (positive when lag currents compared the phase voltages).
Operation and settings
The element is enabled for start and trip on the base of the direction setting for the two independent-
ly programmable thresholds.
Q1> Tripping direction:
Q Forward
:
Q1> Tripping direction:
Q Reverse
:
Q1> Tripping direction:
Q Forward/Reverse
:
The element has two adjustable thresholds with time definite delay.
P
Q
TRIP
Q
1
>
Q1> Tripping direction: Q Forward:
General operation time characteristic for the directional reactive overpower element - 32Q
P
Q
TRIP
Q
1
>
Q1> Tripping direction: Q Reverse:
General operation time characteristic for the directional reactive overpower element - 32Q
P
Q
TRIP
TRIP
Q
1
>
Q
1
>
Q1> Tripping direction: Q Forward/Reverse:
General operation time characteristic for the directional reactive overpower element - 32Q
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021