TECHNICAL DATA
23
(U/f)
>
Element
Setpoints
Curve type ((
U/f
)
>
Curve
)
DEFINITE, IEC/BS A, B, C
Reset time delay (
t
P2
>
RES
)
0.00...1000 s
0.00...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...1000 s (step 1 s)
Definite time
First threshold definite time (
U/f
)>
def
0.50...2.00
U
n
/f
n
(step 0.01
U
n
/f
n
)
Operating time (
t
(U/f)
>
def
)
0.10...100.0
s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Inverse time
First threshold inverse time (
U/f
)>
inv
0.50...2.00
U
n
/f
n
(step 0.01
U
n
/f
n
)
Operating time (
t
(U/f)
>
def
)
0.10...60.0
s
11
0.10...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
(U/f)
>>
Element
Definite time
First threshold definite time (
U/f
)>>
def
0.50...2.00
U
n
/f
n
(step 0.01
U
n
/f
n
)
Operating time (
t
(U/f)
>>
def
) 0.10...100.0
s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤ 0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤ 0.05 s
Overshoot time
0.04 s
Pickup
accuracy ±
0.5% on voltage measures
±
5 mHz on frequency measures
Operate time accuracy
5% ± 10 ms
—
Thermometric probes - 26
12
Alarm ThAL1...8:
Alarm threshold (
Th
AL1...8
) 0...200
°C
Operate time (t
Th
AL1...8
)
0....100
s
Trip Th>1...8:
Trip threshold (
Th>
1...8
)
0...200
°C
Operate time (t
Th>
1...8
)
0....100
s
—
Undervoltage - 27
Common configuration:
Voltage measurement type (
U
type27)
13
U
ph-ph
/
U
ph-n
Operating logic (
Logic
27) AND/OR
U< Element
Curve type (
U
<
Curve
)
DEFINITE/INVERSE
14
Definite time
First threshold definite time (
U<
def
)
0.05...1.10
U
n
/
E
n
(step 0.01
U
n
/
E
n
)
Operating time (
t
U
<
def
)
0.03...100.0
s
0.03...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Inverse time
First threshold inverse time (
U<
inv
)
0.05...1.10
U
n
/
E
n
(step 0.01
U
n
/
E
n
)
Operating time (
t
U
<
inv
)
0.10...100.0
s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
U<< Element
Definite time
Second threshold definite time (
U<<
def
)
0.05...1.10
U
n
/
E
n
(step 0.01
U
n
/
E
n
)
Operating time (
t
U
<<
def
)
0.03...100.0
s
0.03...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Pickup time
≤
0.04 s
Dropout
ratio
1.03...1.05
Dropout time
≤
0.05 s
Nota 12 Optional function
Note 13 With
U
ph-ph
setting all thresholds are in p.u.
U
n
With
U
ph-n
setting all thresholds are in p.u
E
n
Note 14 The mathematical formula for INVERSE curve is: t= (0.75 ∙
t
U
<
inv
) / [1 - (
U
/
U
<
inv
)]
t :
operating time (in seconds)
t
U
<
inv
: operating time setting (referred to
U
/
U
<
inv
= 0.25 )
U :
input voltage
U<
inv
: threshold setting
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021