![Thytronic XMR-A 4l+1A Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/thytronic/xmr-a-4l-1a/xmr-a-4l-1a_manual_1113984041.webp)
TECHNICAL DATA
41
CLP activation time (
t
PDCLP>>>>
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (
t
PD
>>>>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time for CTs input versions
Fourth threshold definite time (
I
PD
>>>>
def
) 0.100...40.0
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...40.0
I
n
(step 0.1
I
n
)
Characteristic angle (
Theta
PD>>>>def
)
0...359°
(step 1°)
I
PD
>>>>
def
within CLP (
I
PDCLP>>>>def
) 0.100...40.0
I
n
0.100...0.999
I
n
(step 0.001
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...40.0
I
n
(step 0.1
I
n
)
Operating time (
t
PD
>>>>
def
)
0.05...10.00 s (step 0.01 s)
Definite time
for ThySensor input versions
Fourth threshold definite time (
I
PD
>>>>
def
) 0.010...30.0
I
n
0.010...0.999
I
n
(step 0.001
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...30.0
I
n
(step 0.1
I
n
)
Characteristic angle (
Theta
PD>>>>def
)
0...359°
(step 1°)
I
PD
>>>>
def
within CLP (
I
PDCLP>>>>def
) 0.010...30.0
I
n
0.010...0.999
I
n
(step 0.001
I
n
)
1.00...9.99
I
n
(step 0.01
I
n
)
10.0...30.0
I
n
(step 0.1
I
n
)
Operating time (
t
PD
>>>>
def
)
0.05...10.00 s (step 0.01 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot time
0.04 s
Pickup accuracy (current measures)
±
0.5% with 0.1
I
n
±
0.2% with 1
I
n
Pickup accuracy (voltage measures)
±
0.5% with 0.1
U
n
±
0.2% with 1
U
n
Operate time accuracy
5% ± 10 ms
—
Directional earth fault overcurrent- 67N
Common configuration for CTs input versions:
67N Operating mode (
Mode67N
)
I
/
I
∙
cos
Residual voltage measurement type for 67N - direct/calculated (
3VoType67N
)
U
E
/
U
EC
67N Multiplier of threshold for insensitive zone (
M
)
1.5...10.0
(step 0.1)
67N Operation from 74VT internal (
74VTint67N
)
OFF/Block/Not
directional
67N Operation from 74VT external (
74VText67N
)
OFF/Block/Not directional
Common configuration for ThySensor input versions:
67N Operating mode (
Mode67N
)
I
/
I
∙
cos
Residual voltage measurement type for 67N - direct/calculated (
3VoType67N
)
U
EC
67N Multiplier of threshold for insensitive zone (
M
)
1.5...10.0
(step 0.1)
67N Operation from 74VT internal (
74VTint67N
)
OFF/Block/Not
directional
67N Operation from 74VT external (
74VText67N
)
OFF/Block/Not directional
I
ED
> Element
I
ED
>
Curve type
(
I
ED
>
Curve)
DEFINITE
IEC/BS A, B, C, ANSI/IEEE MI, VI, EI, EM
CLP operating mode (
I
EDCLP
>
Mode)
OFF/ON-Element blocking/ON-Change setting
CLP activation time
(
t
EDCLP>
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Reset time delay (
t
ED
>
RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Definite time
First threshold definite time (
I
ED>def
-
U
ED>def
)
Residual current pickup value
0.002...10.00
I
En
0.002...0.999
I
En
(step 0.001
I
En
)
1.00...10.00
I
En
(step 0.01
I
En
)
Residual voltage pickup value
0.004...0.500
U
En
(step 0.001
U
En
)
Characteristic
angle
0...359°
(step 1°)
Half operating sector
1...180°
(step 1°)
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021