FUNCTION CHARACTERISTICS
75
—
Communication interfaces
Several communication ports are provided:
• One Ethernet/RS232 port on front side for local communication (ThyVisor)
• One RS485 port on the rear side for bus communication
• Two Ethernet ports on rear side for network communication
Local port
The local port has high priority compared with the remote Ethernet and RS485 ports.
The local port is the simplest access for setting by means the ThyVisor software.
RS485
Several protocol are implemented:
• ModBus RTU. Modbus is a serial communications protocol. It is a de facto standard commu-
nications protocol in industry, and is now the most commonly available means of connecting
industrial electronic devices also inside electric utilities and substation.
• IEC 60870-5. The IEC 60870-5 suite of protocol is used for communications from master station to
substation, as well within the substation; the IEC 60870-5-103 (Protection equipment) is available
together the Modbus protocol on some version of XMR devices (code XMRxx#xxxxC x).
Ethernet
It is provided a communication board useful for Ethernet communication with ModBus TCP/IP
[1]
or
IEC61850 protocol
When ordering the types of network board may be selected:
[2]
• Two TX ports module (RJ45 copper network) with multiplexed operation mode.
• Two FX ports module (optical fiber network) with multiplexed operation mode
• One FX port + RS485
• One port TX + RS485
• One port RS485
Modbus/TCP basically embeds a Modbus frame into a TCP frame in a simple manner. This is a con-
nection-oriented transaction which means every query expects a response.
This query/response technique fits well with the master/slave nature of ModBus, adding to the de-
terministic advantage that Switched Ethernet offers industrial users.
In the same way as the RS485 base Modbus, every device is identified by a personal address and the
communication goes in “client-server” mode with answering request from the receiver.
The protective relay can be directly connect to the Ethernet network (no gateway, protocol converter
are needed).
No HW preset are required.
Note 1 Information about the ModBus map may be find inside the “Remote programming manual”
Note 2 Under normal conditions, the primary port is active, while the secondary port is activated automatically in the event of failure of the primary port
or with hw-sw switching command
serial-sch.ai
RJ45 Connector
ethernet-sch.ai
Connector TX (RJ45 copper)
Connector FX (Optical Fibre)
RX
TX
Ethernet
RS485
7
6
A+
B-
FTP shielded cable Cat.5e or higher
B-
A+
RS485
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021