FUNCTION CHARACTERISTICS
173
The element can be enabled or disabled by setting
ON
or
OFF
the
State
parameter inside the
Set \
Profile A (or B) \ Negative sequence current/positive sequence current ratio-I2/I1 \ I21> Element \ De-
finite time
menu.
Breaker failure (BF)
I
2
/I
1
> threshold can be associated to BF (H) and BF (L) protection by activating the relative parameter
in the matrices “Selection of function tripping for BF (H)” or “Selection of function tripping for BF (L)”
in relevant
BF
menus
1
:
• Set \ Profile A (or B) \ Breaker failure - BF side H
• Set \ Profile A (or B) \ Breaker failure - BF side L
Second harmonic restraint
A block from the second harmonic restraint may be set by setting
ON
the parameter insi-
de the
Set \ Profile A (or B) \ Negative sequence current/positive sequence current ratio-I2/I1 \
I21> Element \ Setpoints
menu
.
Cold load pickup
If the CLP function (Cold Load Pick-up) is enabled for element blocking, the selected threshold may
be blocked for an adjustable time interval, starting from the circuit breaker closure.
This operating mode may be select by setting
ON-Element blocking
the
I21CLP> Mode
para-
meter.
If the CLP function (Cold Load Pick-up) is enabled for threshold change, the selected threshold may
be changed for an adjustable time interval, starting from the circuit breaker closure. This operating
mode may be select by setting
ON-Change setting
the
I21CLP> Mode
parameter, whereas the
operating thresholds within the CLP may be adjusted inside the
Set \ Profile A (or B) \ Negative se-
quence current/positive sequence current ratio-I2/I1 \
I
21> Element \ Definite time
menu.
For both operating modes the CLP Activation time parameter (
t21CLP>
) may be adjusted insi-
de the
Set \ Profile A (or B) \ Negative sequence current/positive sequence current ratio-I2/I1 \
I21> Element \ Setpoints
menu.
CT Supervision (74CT)
The element may be blocked when the CT supervision function become active to avoid unwanted
trips following any faults on CTs an amperometric input circuits;
2
the
74CT Enable
parameter may
be set to
ON
inside the
Set \ CT supervision-74CT
menu.
All parameters can be set separately for A and B setting profiles.
Logical block (Block1)
If the
I21>BLK1
enabling parameter are set to
ON
and a binary input is designed for logical block
(Block1), the protection is blocked off whenever the given input is active.
The trip timer is held in reset condition, so the operate time counting starts when the input block
goes down.
3
The enabling parameter is available inside the
Set \ Profile A (or B) \ Negative sequence
current/positive sequence current ratio-I2/I1 \ I21> Element \ Setpoints
menu, while the
Block1
function must be assigned to the selected binary input inside the
Set \ Board 1(2) inputs \ Binary input
IN1-1...(IN1-x)
menus.
Note 1 The common settings concerning the Breaker failure protection are adjustable inside the
Breaker Failure - BF
menu.
Note 2 The setting may be found in the “CT supervision ” paragraph inside CONTROL AND MONITORING section
Note 3 The description of the logical block (Block 1) function may be found in the “Logic Block” paragraph inside CONTROL AND MONITORING section
I
2
/
I
1
t
21
>
(
I
2
/
I
1
)
>
t
General operation time characteristic for negative sequence-positive sequence ratio element - I2/I1
TRIP
General logic diagram of the negative sequence-positive sequence ratio element - I2/I1
all-FI2-I1.ai
(I2/I1)
(I2/I1)> Element
Start (I2/I1)>
Start (I2/I1)>
Trip (I2/I1)>
t
21
>
def
(I2/I1)>
def
Enable (I2/I1)>
Block1
BLK1(I2/I1)>
&
I<<BLK1
&
Start I2ndh>
&
(I2/I1)>2ndh-REST
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021