3 - 4
3. SIGNALS AND WIRING
Note 1. The built-in regenerative resistor is provided for LECSA1-S3 and LECSA2-S4. (Factory-wired.) When using the regenerative
option, refer to section 11.2.
2. For encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
3. For the sink I/O interface.
For the source I/O interface, refer to section 3.8.3.
4. Refer to section 3.10.
5. Configure the circuit to shut off the main circuit power supply by an external sequence simultaneously with the forced stop
(EM1) turning OFF.
6. Be sure to use a magnetic contactor (MC) with an operation delay time of 80ms or less. The operation delay time is the time
interval between current being applied to the coil until closure of contacts.
7. Use the enhanced insulation power supply for the control circuit power supply 24VDC. In addition, do not use a power supply
with an output voltage starting time of one second or more.