13. POSITIONING MODE
(c) Automatic continuous positioning operation
When "1" or "3" is set to the auxiliary function in the point table, positioning of the next point table No. is
executed continuously.
When "1" or "3" is set to the auxiliary function in the point tables up to No.6, a maximum of 7 points of
automatic continuous positionings are possible. Set "0" to the auxiliary function in the last point table.
As an example, the operation in the absolute value command system is shown using the set values in
the following table. Here, the point table No.1 uses the absolute value command system, the point table
No.2 the incremental value command system, and the point table No.3 the absolute value command
system.
Point table No.
Position data
(Target position)
[×10
STM
μm]
Servo motor
speed [r/min]
Acceleration
time constant
[ms]
Deceleration
time constant
[ms]
Dwell
[ms]
Auxiliary
function
1
5.00
3000
100
150
100
1
2
-6.00
2000
100
100
0
3
3
3.00
3000
50
50
0
0 (Note)
Note. Always set "0" or "2" to the auxiliary function in the last point table among the consecutive point tables.
0: When point table is used in absolute value command system
2: When point table is used in incremental value command system
Point table
No.1
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
6ms or more
Servo-on (SON)
Ready (RD)
Trouble (ALM)
Automatic/manual
selection (MD0)
In-position (INP)
Rough match (CPO)
Point table No.
Servo motor
speed
Forward
rotation
Reverse
rotation
0r/min
ON
OFF
Forward rotation start
(ST1)
1
ON
OFF
(Note 2)
Travel completion
(MEND)
Point table No. output
(PT0 to PT2)
3ms or less
Point table
No.2
Point table
No.3
1
(Note 1)
6ms or
more
Note 1. External input signal detection delays by the input filter setting time of parameter No. PD19. Additionally, make up a
sequence that changes the point table selection ahead of time by considering delays in output signal sequence from the
PC or PLC...etc and variations of a signal change due to hardware.
2. If the over load tough drive function is enabled by setting parameter No. PA04 to " 1", INP turn-on delays during the
overload tough drive. MEND turn-on also delays together with INP. However, MEND does not turn ON during automatic
continuous positioning operation.