13 - 86
13. POSITIONING MODE
No.
Symbol
Name and function
Initial
value
Setting
range
Unit
PE16
LMPL
Software limit +
Used to set the address increment side software stroke limit. The software
limit is made invalid if this value is the same as in "software limit -". (Refer to
(4) in this section.)
Set the same sign to parameters No. PE16 and No. PE17. Setting of
different signs will result in a parameter error.
Upper three digits
Lower three digits
Parameter No. PE16
Parameter No. PE17
Set address:
The software limit + is a set of upper digits and lower digits. To change the
value, set in the order of lower digits to upper digits.
0
-999999
to
999999
×10
STM
μm
PE17
LMPH
PE18
LMNL
Software limit -
Used to set the address decrement side software stroke limit. The software
limit is made invalid if this value is the same as in "software limit +". (Refer
to (4) in this section.)
Set the same sign to parameters No. PE18 and No. PE19. Setting of
different signs will result in a parameter error.
Upper three digits
Lower three digits
Parameter No. PE18
Parameter No. PE19
Set address:
The software limit - is a set of upper digits and lower digits. To change the
value, set in the order of lower digits to upper digits.
0
-999999
to
999999
×10
STM
μm
PE19
LMNH
PE20
*LPPL Position range output a
Used to set the address increment side position range output address.
Set the same sign to parameters No. PE20 and No. PE21. Setting of
different signs will result in a parameter error.
In parameters No. PE20 to PE23, set the range where position range (POT)
turns on.
Upper three digits
Lower three digits
Parameter No. PE20
Parameter No. PE21
Set address:
Position range output a is a set of upper digits and lower digits. To
change the value, set in the order of lower digits to upper digits.
0
-999999
to
999999
×10
STM
μm
PE21
*LPPH