4 - 43
4. PARAMETERS
Specify the alarm No. in parameter No. PC44 when operating the drive recorder with the specific alarm No.
Specification of alarm No.
00 : No specification
(The optimum item is recorded according to the alarms that have occurred
ea rlier and operating conditions.)
01 to FFh : Specification
(The specified item is recorded when an alarm of the specified alarm No. occurs.)
When a non-existent alarm No.
is specified, the specified value is recognized as
"00h ".
Parameter No. PC44
0
(2) Record data
(a) When the set value of parameter No. PC44 is " 00":
1) When alarms to be recorded by the drive recorder function are in the alarm history:
The specified data are automatically selected and recorded based on the alarm history.
a) Analog CH data
Three data for 3CH are automatically selected from the data listed below.
Servo motor speed [r/min]
Torque [%]
Bus voltage (Note)
Within one-revolution position [pulse]
Multi-revolution counter [rev]
Current command [%]
Regenerative load ratio [%]
Command pulse frequency [kpps]
Effective load ratio [%]
Note. The bus voltage is displayed in five steps.
Display value
Description
5
Overvoltage (About 400V or more)
4
High voltage (About 375V or more)
3
Normal
2
Low voltage (About 200V or less)
1
Undervoltage (About 160V or less)
b) Digital CH (4CH) data
Four data for 4CH are automatically selected from the data listed below.
Trouble (ALM)
Forced stop (EM1)
Servo-on (SON)
Electromagnetic brake interlock (MBR)
Main circuit power supply OFF
Ready (RD)
Limiting torque (TLC)
2) When alarms to be recorded by the drive recorder function are not in the alarm history:
The data to be recorded are as indicated in the following table.
Analog CH data
Digital CH data
Sampling time
[ms]
Measuring
length [ms]
(64 points)
CH1
(trigger)
CH2
CH3
CH4
CH1 Servo motor speed [r/min]
CH2 Torque [%]
ALM
EM1
SON
RD
0.8
56.8
CH3 Within one-revolution position [pulse]