App. - 12
APPENDIX
(7) Auxiliary equipment and options
(a) The no-fuse breaker and magnetic contactor used should be the EN or IEC standard-compliant
products of the models described in LECSA - DRIVER MANUAL. Use a type B leakage current
breaker (RCD). When it is not used, provide insulation between the driver and other device by double
insulation or reinforced insulation, or install a transformer between the main circuit power supply and
driver.
(b) The sizes of the cables described in LECSA - DRIVER INSTRUCTION MANUAL meet the following
requirements. To meet the other requirements, follow Table 5 and Appendix C in IEC/EN60204-1.
Ambient temperature: 40(104) [°C(°F)]
Sheath: PVC (polyvinyl chloride)
Installed on wall surface or open table tray
(c) Use the EMC filter for noise reduction.
(8) Performing EMC tests
When EMC tests are run on a machine/device into which the driver has been installed, it must conform to
the electromagnetic compatibility (immunity/emission) standards after it has satisfied the operating
environment/electrical equipment specifications.
For the other EMC directive guidelines on the converter unit and driver (drive unit), refer to the EMC
Installation Guidelines (IB(NA)67310).