2.13.2 Setting Notes
General
The forward active power protection is only effective and available if this function was
set on protective functions configuration (section 2.2, address
132
,
FORWARD POWER
= to
Enabled
. If the function is not required
Disabled
is set. The address
3201
FORWARD POWER
serves to switch the function
ON
or
OFF
or to block only the trip
command (
Block relay
).
Pickup Values,
Time Delays
The setting of the forward power protection depends very much on the intended pur-
pose. General setting guidelines are not possible. The pickup values are set in percent
of the secondary apparent power rating S
Nsec
=
√
3 · U
Nsec
· I
Nsec
. Consequently, the
machine power must be converted to secondary quantities:
with
Psec
Secondary power corresponding to setting value
S
Nsec
Secondary rated power =
√
3 · U
Nsec
· I
Nsec
P
Mach
Machine power corresponding to setting value
S
N, Mach
Nominal apparent power of the machine
U
N, Mach
Nominal voltage of the machine
I
N Mach
Nominal current of the machine
U
N prim
Primary Nominal Voltage of the voltage transformers
I
N prim
Nominal primary CT current
Address
3202
serves to set the threshold of the forward power to an undershoot (
Pf<
)
and address
3204
(
Pf>
) serves to set it to overshoot. Addresses
3203
T-Pf<
and
3205
T-Pf>
serve to set the associated time delays.
In address
3206
MEAS. METHOD
the user can select whether a fast or a precise mea-
suring procedure is to be used for the forward power calculation. In most cases, the
precise measuring procedure is preferred in the power station sector (as a rule),
whereas the fast procedure is applied for use as mains decoupling.
The set times are additional time delays not including the operating times (measuring
time, drop-out time) of the protective function.
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...