4.25 Operating Ranges of the Protection Functions
343
7UM61 Manual
C53000-G1176-C127-3
4.25 Operating Ranges of the Protection Functions
Operational condi-
tion 0
Operational condition 1
Operational condi-
tion 0
Protection function
f
≤
0 Hz
11 Hz < f/Hz
≤
40
40 Hz
≤
f/Hz
≤
69
f
≥
70 Hz
Definite-Time Overcurrent Protection
(ANSI 50,51,67)
active
active
active
active
Inverse-Time Overcurrent Protection
(ANSI 51V)
inactive
active
active
inactive
Thermal Overload Protection (ANSI 49)
inactive
active
active
inactive
Unbalanced Load (Negative Sequence)
Protection (ANSI 46)
inactive
active
active
inactive
Underexcitation (Loss-of-Field) Protection
(ANSI 40)
inactive
active
active
inactive
Reverse Power Protection (ANSI 32R)
inactive
active
active
inactive
Forward Active Power Supervision (ANSI
32F)
inactive
active
active
inactive
Impedance Protection (ANSI 21)
inactive
active
active
inactive
Undervoltage Protection (ANSI 27)
inactive
active
active
inactive
Overvoltage Protection (ANSI 59)
active
active
active
active
Frequency Protection (ANSI 81)
inactive
active
active
inactive
Underfrequency protection
inactive
active
active
inactive
Overexcitation (Volt/Hertz) Protection
(ANSI 24)
inactive
active
active
inactive
Rate-of-Frequency-Change Protection
df/dt (ANSI 81R)
inactive
active
active
inactive
Jump of Voltage Vector
inactive
active
active
inactive
90-%-Stator Earth Fault Protection (ANSI
59N, 64G, 67G)
active
active
active
active
Sensitive Earth Fault Protection (ANSI
51GN, 64R)
inactive
active
active
inactive
100-%-Stator Earth Fault Protection with
3rd Harmonics (ANSI 27/59TN 3rd Harm.)
inactive
active
active
inactive
Motor Starting Time Supervision (ANSI
48)
inactive
active
active
inactive
Restart Inhibit for Motors (ANSI 66,
49Rotor)
inactive
active
active
inactive
Breaker Failure Protection (ANSI 50BF)
inactive
active
active
inactive
Inadvertent Energization (ANSI 50, 27)
active
active
active
active
Threshold supervision
inactive
active
active
inactive
External Trip Functions
active
active
active
active
RTD-Box
active
active
active
active
Operational Condition 1:
At at least one of the measuring inputs (I
L1
, I
L2
, I
L3
, U
L1
, U
L2
U
L3
) of the device, at least
5% of the rated voltage is present so that the sampling frequency for the measured
value processing can be adjusted.
Operational Condition 0:
If no suitable measured values are present, or if the frequency is below 11 Hz or above
70 Hz, the device cannot operate (operational condition 0) and no measured value
processing occurs.
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...