4 Technical Data
332
7UM61 Manual
C53000-G1176-C127-3
4.18 100-%-Stator Earth Fault Protection with 3rd Harmonics (ANSI
27/59TN 3rd Harm.)
Setting Ranges / Increments
Times
Dropout Ratios
Tolerances
Influencing Variables
Pickup Value for 3rd Harmonic in Undervolt-
age Stage U
0 (3. Harmon.)
<
0.2 V to 40.0 V
Increments 0.1V
Pickup Value for 3rd Harmonic in Undervolt-
age Stage U
0 (3. Harmon.)
>
0.2 V to 40.0 V
Increments 0.1V
Delay Time T
SEF (3rd HARM)
0.00 s to 60.00 s
or
∞
(ineffective)
Increments 0.01 s
Enabling conditions
P/P
min
>
0 % to 100 %
or (ineffective)
Increments 1 %
U/U
1 min
>
50.0 V to 125.0 V
or (ineffective)
Increments 0.1V
Pickup Times
approx. 80 ms
Dropout Times
approx. 80 ms
Undervoltage stage U0 (3rd Harmon.)<
approx. 1.10 or 0.1 mA
Overvoltage stage U0 (3rd Harmon.)>
approx. 0.90 or 0.1 mA
Enabling conditions
P/P
min
>
approx. 0.90
U/U
1 min
>
approx. 0.95
Displacement Voltage
3 % of setting value or 0.1 V
Delay Time T
SEF (3rd HARM)
1 % of setting value or 10 ms
Power Supply DC Voltage in Range
0,8
≤
U
PS
/U
PSN
≤
1.15
≤
1 %
Temperature in Range
23
°
F or –5
°
C
≤
Θ
amb
≤
131
°
F or 55
°
C
≤
0.5 % / 10 K
Frequency in Range
0,95
≤
f/f
N
≤
1.05
≤
1 %
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...