![Siemens Siprotec 7UM611 Скачать руководство пользователя страница 84](http://html.mh-extra.com/html/siemens/siprotec-7um611/siprotec-7um611_manual_383128084.webp)
2 Functions
84
7UM61 Manual
C53000-G1176-C127-3
2.11.4 Information List
3011
T SHRT Uex<
0.00 .. 60.00 sec;
∞
0.50 sec
T-Short Time Delay (Char. &
Uexc<)
3014A
Umin
10.0 .. 125.0 V
25.0 V
Undervoltage blocking Pickup
No.
Information
Type of In-
formation
Comments
5323
>Exc. BLOCK
EM
>BLOCK underexcitation protection
5327
>Char. 3 BLK.
EM
>BLOCK underexc. prot. char. 3
5328
>Uexc fail.
EM
>Exc. voltage failure recognized
5329
>Char. 1 BLK.
EM
>BLOCK underexc. prot. char. 1
5330
>Char. 2 BLK.
EM
>BLOCK underexc. prot. char. 2
5331
Excit. OFF
AM
Underexc. prot. is switched OFF
5332
Excit.BLOCKED
AM
Underexc. prot. is BLOCKED
5333
Excit.ACTIVE
AM
Underexc. prot. is ACTIVE
5334
Exc. U< blk
AM
Underexc. prot. blocked by U<
5336
Uexc failure
AM
Exc. voltage failure recognized
5337
Exc< picked up
AM
Underexc. prot. picked up
5343
Exc<3 TRIP
AM
Underexc. prot. char. 3 TRIP
5344
Exc<1 TRIP
AM
Underexc. prot. char. 1 TRIP
5345
Exc<2 TRIP
AM
Underexc. prot. char. 2 TRIP
5346
Exc<U<TRIP
AM
Underexc. prot. char.+Uexc< TRIP
Addr.
Parameter
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...