2.14 Impedance Protection (ANSI 21)
93
7UM61 Manual
C53000-G1176-C127-3
Loop Selection
• The corresponding phase-earth loop is used for a 1-pole pickup.
• With a 2-pole pickup, the phase-phase loop with the corresponding phase-to-phase
voltage is used for impedance calculation.
• With a 3-pole pickup, the phase-phase loop with the highest current value is used
and with equal current amplitudes, the procedure described in the last row of the
following of table is applied.
Table 2-5
Measuring Loop Selection
This loop selection type ensures that the fault impedance of system faults is measured
correctly via the unit transformer. A measuring error occurs with a 1-pole system short-
circuit, since the zero phase-sequence system is not transmitted via the machine
transformer (switching group e.g. Yd5). The following table describes the fault model-
ing and the measuring errors.
Table 2-6
Fault Modeling and Measuring Errors on the Generator Side on System Faults
Pickup
Measuring Loop
1-pole
L1
L2
L3
Phase-earth
L1–E
L2–E
L3–E
2-pole
L1, L2
L2, L3
L3, L1
Phase-phase,
Calculation of U
I
I
and
I
I
I
L1– L2
L2– L3
L3– L1
3-pole,
with different ampli-
tudes
L1,2*L2,L3
L2.2*L3,L1
L3.2*L2,L3
Phase-ground, se-
lection of loop with
the highest current
U
I
(Imax)
and
I
I
(
I
max)
L2–E
L3–E
L1–E
3-pole,
with equal ampli-
tudes
L1, L2, L3
Phase-earth, any,
maximum current
amount
L1=
I
L2=
I
L3 then
I
L1
I
L1=
I
L2 >
I
L3 then
I
L1
I
L2=
I
L3 >
I
L1 then
I
L2
I
L3=
I
L1 >
I
L2 then
I
L1
System Faults Fault Model on
the Generator
Side
Loop Selection
Measuring
Errors
3–pole short
circuit
3–pole short
circuit
Phase-earth
always correct
measurement
2–pole short
circuit
3–pole short
circuit
Phase-earth loop
with highest
current
always correct
measurement
1–pole short
circuit
2–pole short
circuit
Phase-phase
loop
Impedance mea-
sured too high by
the zero imped-
ance
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...