2.27 Inadvertent Energization (ANSI 50, 27)
163
7UM61 Manual
C53000-G1176-C127-3
Figure 2-60
Logic Diagram of the Inadvertent Energizing Protection (Dead Machine Protec-
tion)
2.27.2 Setting Notes
General
Inadvertent energizing protection is only effective and available if address
171
INADVERT. EN.
is set to
Enabled
during configuration. If the function is not required
Disabled
is set. Address
7101
INADVERT. EN.
serves to switch the function
ON
or
OFF
or to block only the trip command (
Block relay
).
Criteria
Parameter
7102
I STAGE
serves to specify the current pickup threshold of the inad-
vertent energization protection function. As a rule, this threshold value is set more sen-
sitively than the threshold value of the time-overcurrent protection. In this case, the in-
advertent energizing protection may only be effective if the device is either in
operational condition 0 or if no nominal conditions have been reached yet. The param-
eter
7103
RELEASE U1<
serves to define these nominal conditions. The typical
setting is about 50 % to 70 % of the nominal voltage. The parameter value is based
on phase-to-phase voltages. A 0 V setting deactivates the voltage tripping. However,
this should only be used if
7102
I STAGE
shall be used as 3rd time-overcurrent pro-
tection stage, at a very high setting.
The parameter
7104
PICK UP T U1<
parameter represents the time delay for the
release of the tripping condition with undervoltage. The user should select a higher
value for this time delay than for the tripping time delay of the time-overcurrent protec-
tion.
The delay time to block the tripping conditions when the voltage is above the under-
voltage threshold is set at
7105
DROP OUT T U1<
. The inadvertent energizing pro-
tection is blocked only after this time in order to enable a tripping subsequent to con-
nection.
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...