4 Technical Data
328
7UM61 Manual
C53000-G1176-C127-3
4.14 Rate-of-Frequency-Change Protection df/dt (ANSI 81R)
Setting Ranges / Increments
Times
Dropout Ratios
Tolerances
Influencing Variables for Pickup Values
Stages, can be +df/dt> or –df/dt
4
Pickup values df/dt
0.1 to 10 Hz/s
Increments 0.1 Hz/s
Delay times T
0.00 to 60.00 s
Increments 0.01 s
or ineffective
Undervoltage Blocking U1>
10.0 to 125.0 V
Increments 0.1 V
Window Length
1 to 25 cycles
Pickup Times df/dt
Approx. 150 ms to 500 ms
(dep. on window length)
Dropout Times df/dt
approx. 150 ms to 500 ms
(dep. on window length)
Dropout Difference
∆
f/dt
0.02 to 0.99 Hz/s (settable)
Dropout Ratio
approx. 1.05
Frequency Rise
–Measuring Window < 5
approx. 5 % or 0.15 Hz/s at U > 0.5 U
N
– Measuring Window
≥
5
approx. 3 % or 0.1 Hz/s at U > 0.5 U
N
Undervoltage Blocking
1 % of setting value or 0.5 V
Delay Times
1 % or 10 ms
Power Supply DC Voltage in Range
0.8
≤
U
PS
/U
PSN
≤
1.15
≤
1 %
Temperature in Range
23
°
F or –5
°
C
≤
Θ
amb
≤
131
°
F or 55
°
C
≤
0.5 % / 10 K
Harmonics
- Up to 10 % 3rd harmonic
- Up to 10 % 5th harmonic
≤
1 %
≤
1 %
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...