4 Technical Data
334
7UM61 Manual
C53000-G1176-C127-3
4.20 Restart Inhibit for Motors (ANSI 66, 49Rotor)
Setting Ranges / Increments
Restart Threshold
Restart Times
Motor starting current relative to Nominal
Motor Current
I
Start
/
I
Motor Nom
1.5 to 10.0
Increments 0.1
Max. admissible Startup Time
T
Start Max
3.0 s to 120.0 s
Increments 1 s
Leveling Time
T
LEVEL
0.0 min to 60.0 min
Increments 0.1 min
Maximum admissible Number of Warm Starts
n
WARM
1 to 4
Increments 1
Difference between Cold and Warm Starts
n
Cold
– n
Warm
1 to 2
Increments 1
Extension Factor at Standstill
k
τ
STANDSTILL
1.0 to 100.0
Increments 0.1
Extension Factor on Motor Operation
k
τ
OPERATION
1.0 to 100.0
Increments 0.1
Minimum Restart Inhibit Time
0.2 to 120.0 min
Increm. 0.1 min
Significance:
Θ
Re.Inh.
Temperature limit below which a restart is possible
Θ
L max adm
maximum admissible rotor overtemperature (= 100 % of operational
value
Θ
L
/
Θ
L
from)
n
cold
number of admissible starts from cold
T
Wait Time
Time after which motor may be reswitched on
T
Leveling
Leveling time during which the thermal replica is "frozen"
T
Re.Inh.
Time until the thermal replica is again below the restart threshold
depends on:
Θ
Hist
Rotor temperature past history
t
Rotor time constant, internally calculated
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...