4.21 Breaker Failure Protection (ANSI 50BF)
335
7UM61 Manual
C53000-G1176-C127-3
4.21 Breaker Failure Protection (ANSI 50BF)
Setting Ranges / Increments
Times
Tolerances
Influencing Variables for Pickup Values
Pickup thresholds BF I>
for
I
N
= 1 A
0.04 A to 2.00 A
Increments
0.01 A
for
I
N
= 5 A
0.20 A to 10.00 A
Increments
0.05 A
Delay Time BF-T
0.06 s to 60.00 s or
∞
Increments 0.01
s
Pickup Times
– On Internal Start
– Using Controls
– For external Start
Dropout Time
approx. 50 ms
approx. 50 ms
approx. 50 ms
approx. 50 ms
Pickup Threshold BF I>
for
I
N
= 1 A
1 % of setting value or 10 mA
for
I
N
= 5 A
1 % of setting value or 50 mA
Delay Time BF-T
1 % or 10 ms
Power Supply DC Voltage in Range
0,8
≤
U
PS
/U
PSN
≤
1.15
≤
1 %
Temperature in Range
–5
°
C
≤
Θ
amb
≤
55
°
C
≤
0.5 % / 10 K
Frequency in Range
0,95
≤
f/f
N
≤
1.05
≤
1 %
Harmonics
– Up to 10 % 3rd harmonic
– Up to 10 % 5th harmonic
≤
1 %
≤
1 %
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...