POWER LIMITER

three-phase

Do not dispose of this device in the trash along with other waste! 

According 

to the Law on Waste, electro coming from households free of charge and can 
give any amount to up to that end point of collection, as well as to store the 
occasion of the purchase of new equipment (in accordance with the principle 
of old-for-new, regardless of brand). Electro thrown in the trash or abandoned 
in nature, pose a threat to the environment and human health.

OM-630

5

9 0 8 3 1 2

5 9 6 4 4 8

- 4 -

- 3 -

Purpose

Installation

The  OM-630  power  consumption  limiter  is  designed  for  conti

-

nuous  monitoring  of  the  power  consumption  of  the  receivers 
connected  to  the  three-phase  network.  The  limiter  allows  to 
disconnect the receivers in case of exceeding the specified power 
consumption. In addition, the OM-360 controller is equipped with 
the  power  supply  voltage  control  function  and  protects  the 
receiving  installation  from  damage  that  may  occur  due  to  dis

-

connection of the neutral wire (if the neutral wire is disconnected 
before the OM-630 power limiter).

Functioning

The OM-630 relay analyzes the power consumption of the devices 
connected  to  the  receiving  line  on  the  basis  of  continuous 
measurements of voltages connected to terminals L1, L2, L3 and N 
as well as the currents flowing through the built-in current relays. 
When the power consumed by the receivers exceeds the value set 
by the user than after the TON time the K1 relay and load will be 
disconnected. After the TOFF time the K1 relay will reconnect. If 
the power consumption is still exceeded, then after the TON time 
the load will be disconnected again. This sequence can be repeated 
six times, after which the load will be disconnected for 10 minutes. 
After that interval the sequence starts from the beginning.

In addition, the limiter is equipped with the power supply voltage 
control  function  and  when  the  voltage  drops  below  160  V,  or 
exceeds  260  V,  then  the  limiter  will  switch  off  the  K1  relay  and 
disconnect the receivers.

1. Turn off the power supply.
2. Mount the limiter on a DIN rail in distribution box.
3. Connect the controller to the electrical system as shown in the 

diagram below paying particular attention to:
a.  The  order  of  connection  of  the  supply  voltage  phases  - 

connecting phase to the N input may damage the device.

b.  Pull  the  current  wires  through  the  holes  of  the  current 

transformers from bottom to top (the order of the phases 
must be the same as in the case of connecting the voltage 
lines) and connect them to the input of the main contacts of 
the K1 contactor.

c. Connect the receiving line and the receivers to the output of 

the main contacts of the K1 contactor.

d. The K2 relay can be used for indicating the exceeding of the 

preset power.

4. Using a screwdriver, set the parameters of the power limiter 

operation:
a. Start time and time of the interval between activations in the 

event of exceeding the preset power.

b. The level of power limit – the first of the stepping potentio

-

meters  allows  to  adjust  the  rough  power  value  and  the 
second one allows to set the precise power value.

T

ON

T

OFF

10min.

1

2

3

4

5

6

1

2

3

4

5

6

1

...

10min.

T

ON

P

P

Max

K1