Operating the device
Technical data
Indications
The configuration of the OM-630 relay is implemented through
four stepping potentiometers located on the front panel of the
relay:
T - Shutdown delay
OFF
If the power consumption is greater than the maximum value for
the time specified with T parameter then the K1 relay will be
OFF
switched off and the relays will be disconnected.
You can select one of the following values: 2 s – 10 s – 30 s – 1 min –
3 min – 5 min – 10 min – 30 min – 60 min.
T - Time interval
ON
Time for which the K1 relay and the receivers will be switched off
in case of exceeding the preset power level.
You can select one of the following values: 1 s - 2 s - 10 s - 20 s - 60 s
- 90 s - 120 s - 180 s - 240 s.
P - Power (rough)
Defining a preset level of power limit.
Potentiometer P allows you to roughly select one of the power
ZG
sections in the range of 5 to 50 kW.
∆P - Power (precise)
Potentiometer PDOK allows you to precisely adjust the power in
the range of 0 to 4.5 kW
.
The indication of the power limiter operating state is imple
-
mented through four LEDs:
U - power supply
R - relay
>P - exceeding the power
<U>- voltage out of range
T
OFF
T
ON
P
∆
P
U
>P.
R
<U>
1
2
3
4
5
6
N
L1 L2 L3
power supply voltage
3×50÷450V 50Hz
range of controlled power
5÷50kW
precise power setting - step
0.5 kW
load shutdown delay
1÷240 sec
t
ime interval between consecutive starts
2 ÷3600 sec
s
hutdown delay for voltage <160 V
5 sec
s
hutdown delay for voltage >260 V
0,1 sec
s
hutdown delay for overcurrent protection
0,1 sec
o
utput circuits
2×8A (AC-1)
K1 – load control
K2 – i
ndication of exceeding the preset power
v
oltage measurement accuracy
<2% (50÷300V)
c
urrent measurement accuracy
<3% (3÷100A)
working temperature
-25 ÷50°C
d
iameter of the passage of the current transformer
12.5mm
dimensions
6 modules (105mm)
mounting
on TH-35 mm rail
protection level
IP20
Description
The s
ys
tem is w
orking pr
operly - the K1 r
ela
y and load ar
e both swit
ched-on.
Ex
ceeding
of
the
allow
able
pow
er
-
coun
tdown
the
TOFF
time
to
K1
rela
y
shut
down.
K1
rela
y
lock
ed
due
to
6-f
old
ex
ceeding
of
the
pr
eset
pow
er
lev
el.
Coun
tdown
of
the
10
minut
es
in
ter
val
to
the
ne
xt
load
swit
ching-on.
K1
rela
y
lock
ed
due
to
6-f
old
ex
ceeding
of
the
pr
eset
pow
er
lev
el.
Coun
tdown
of
the
10
minut
es
in
ter
val
to
the
ne
xt
load
swit
ching-on.
Pow
er
supply
volt
ag
e
(on
at
leas
t one
phase)
low
er
than
160
V.
Pow
er
supply
volt
ag
e
(on
at
leas
t one
phase)
higher
than
260
V.
-
the LED is of
f
-
the LED is o
n
-
the LED blink
s
U
R
>P
<U>
D131118