2.10 Unbalanced Load (Negative Sequence) Protection (ANSI 46)
71
7UM61 Manual
C53000-G1176-C127-3
Cool Down
A settable cool-down time starts as soon as the constantly permissible unbalanced
load
I2>
is undershot. The tripping drops out on dropout of the pickup threshold drop-
out. However, the counter content is reset to zero with the cooling time parameterized
at address
1705
T COOL DOWN
. In this context, this parameter is defined as the time
required by the thermal image to cool down from 100 % to 0 %. The cool-down time
depends on the construction type of the generator, and especially on the damper wind-
ing. Preloading is taken into consideration when unbalanced loading occurs during the
cool-down period. The protective relay will thus trip in a shorter time.
Tripping Stages
Figure 2-16
Tripping Zone of the Unbalanced Load Protection
Definite Time Trip-
ping Stage
High negative phase sequence currents can only be caused by a phase-to-phase
short circuit in the system which must be covered in accordance with the network
grading plan. For this reason, the thermal characteristic is cut by a selectable, definite
time negative phase-sequence current stage (parameters
1706
I2>>
and
1707
T
I2>>
).
Please also observe the instructions regarding phase sequence changeover in Sec-
tions 2.3 and 2.33.
Logic
The following figure shows the logic diagram for the unbalanced load protection. The
protection may be blocked via a binary input (
“>BLOCK I2”
). Pickups and time
stages are reset and the metered values in the thermal model are cleared. The binary
input
“>RM th.rep. I2”
only serves to clear metered values of the thermal char-
acteristic.
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...