2 Functions
142
7UM61 Manual
C53000-G1176-C127-3
Figure 2-50
Logic Diagram of 100% Stator Earth Fault Protection
2.23.2 Setting Notes
General
The 100% Stator earth fault protection is only fully effective and available if address
152
SEF 3rd HARM.
is set to
Enabled
during configuration. If the function is not
required
Disabled
is set. Address
5201
SEF 3rd HARM.
serves to switch the func-
tion
ON
or
OFF
or to block only the trip command (
Block relay
).
Connection Type
Depending on the system conditions, at address
223
UE CONNECTION
the user spec-
ified during the project configuration if the displacement voltage U
0
is tapped via a
neutral transformer (
neutr. transf.
) or via the broken delta winding of an earthing
transformer (
broken delta
) and fed to the protection device. If it is not possible to
make the displacement voltage available to the protection device as a measured
quantity, computed quantities are used and
Not connected
must be set. The option
any VT
is selected if the voltage input of the 7UM61 is to be used for measuring any
other voltage instead of for earth fault protection. In this case the 100% stator earth
fault protection function is ineffective.
Pickup Value for
3rd Harmonic
Depending on the selection of the connection type, only one of the two setting param-
eters
5202
or
5203
is accessible.
The setting values can only be determined within the framework of a primary test. The
following applies in general:
• The
5202
U0 3.HARM<
undervoltage stage is relevant for a connection to a trans-
former in the starpoint. The pickup value should be chosen as low as possible.
• The
5203
U0 3.HARM>
overvoltage stage is relevant for a connection via the
broken delta winding of an earthing transformer and for a not connected, but inter-
nally calculated displacement voltage.
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...