2.35 Ancillary Functions
213
7UM61 Manual
C53000-G1176-C127-3
In addition, the following are be available:
Minimum and
Maximum Values
Minimum and maximum values for the positive-sequence components I
1
and U
1
, the
active power P, reactive power Q, in primary values, of the frequency f and of the 3rd
harmonic content in the displacement voltage in secondary values U
3.H
. Included are
the date and time they were last updated. The minimum/maximum values can be reset
via binary inputs or, in the delivery status of the device, also via the F4 function key.
Minimum and Maximum Values: only with version 7UM61**
_
*****
_
3***
Power Metered
Values
W
p
, W
q
, metered values of the active and reactive energy in kilowatt, megawatt or gi-
gawatt hours primary or in kVARh, MVARh or GVARh primary, separately according to
the input (+) and output (–), or capacitive and inductive.
The calculation of the operational measured values is also executed during fault. The
values are updated at intervals of
≥
0.3 s and
≤
1 s.
Power Metered Values: only with version 7UM61**
_
*****
_
3***
Transfer of Mea-
sured Values
Measured values can be transferred via the interfaces to a central control and storage
system.
Definition of Power Measurement
The 7UM61 uses the generator reference-arrow system. The power output is positive.
Figure 2-80
Definition of Positive Direction of Reference Arrows
The following table shows the operating ranges for synchronous and asynchronous
machines. For this, parameter
1108
ACTIVE POWER
is set to
Generator
. ”Normal
condition" shows the power under normal operating conditions: + means that a posi-
tive power is displayed on the protective device, – means that the power is negative.
www
. ElectricalPartManuals
. com
Содержание Siprotec 7UM611
Страница 16: ...Contents 16 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 232: ...2 Functions 232 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 292: ...3 Mounting and Commissioning 292 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 410: ...A Appendix 410 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 412: ...Literature 412 7UM61 Manual C53000 G1176 C127 3 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...